Pigtail Terminations

TL-Series motors have a short pigtail cable that connects to the motor, but is not
shielded. The preferred method for grounding the TL-Series power cable on the
motor side is to expose a section of the cable shield and clamp it directly to the
machine frame. The motor power cable also has a 150 mm (6.0 in.) shield
termination wire with a ring lug that connects to the closest earth ground. Use
this method in addition to the cable clamp. The termination wire can be
extended to the full length of the motor pigtail if necessary, but it is best to
connect the supplied wire directly to ground without lengthening.

Figure 54 - Pigtail Terminations

(1) Remove paint from machine frame to be sure of proper HF-bond between machine frame and motor case, shield clamp, and ground

stud.

(1)

(1)

Pigtail Cable

TL-Series

Motor

Connectors

Motor Power Cable

Machine Frame

150 mm (6.0) Termination

Cable Braid Clamped

to Machine Frame.

(1)