Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

263

Enhanced Peak Performance

Appendix F

3. Verify change with another sercos IDN Read Message from IDN P:0:7

and examine bit zero.

Refer to this Logix Designer application example.

DriveExplorer Software

To use DriveExplorer software to change IDN parameter values, you must also
have the 1203-SSS Serial to SCANport adapter. Refer to

Appendix C

on

page 225

for more information on changing IDN parameter values by using this

method.

1. Connect a 1203-SSS Serial to SCANport adaptor to the drive by using

DriveExplorer software.

2. Change parameter P507 [Drv Peak Rating] from 150% to 250% (or 200%

if applicable).

3. Save device values to nonvolatile memory.