83

Connecting the Kinetix 6000 Drive System

Chapter 5

Determine the Input Power
Configuration

Before wiring input power to your Kinetix 6000 system, you must determine the
type of input power you are connecting to. The IAM module is designed to
operate in both grounded and ungrounded environments.

Grounded Power Configurations

The grounded (WYE) power configuration lets you ground your three-phase
power at a neutral point. This type of grounded power configuration is preferred.

Figure 39 - Grounded Power Configuration (WYE Secondary)

Refer to

Power Wiring Examples

beginning on

page 187

for input power

interconnect diagrams with and without the LIM module.

ATTENTION: When using a LIM module with your IAM module, the VAC LINE
input power must come from a grounded configuration (refer to

Figure 39

).

When not using a LIM module with your IAM module, ungrounded
configurations are permitted, but you must set the jumper to the ungrounded
position for proper drive operation.
Refer to Setting the Ground Jumper in Ungrounded Power Configurations on

page 87

for more information.

L3

L2

L1

BAUD

RATE

TX

RX

DPI

1 2 3 4 5 6 7 8 9

DC-

DC+

L3

L2

L1

CONT EN-

CONT EN+

W

V

U

MBRK -

MBRK +

COM

PWR

DBRK -

DBRK +

CTRL 2

CTRL 1

1 2 3 4

1 2 3 4 5 6

1 2

1 2 3 4 5 6

1 2

Transformer

Kinetix 6000 IAM Module,

Top View

Three-phase

Input VAC

Phase Ground

Transformer (WYE) Secondary

Bonded Cabinet

Ground

Ground Grid or

Power Distribution Ground

Connect to power rail
ground stud.

Three-phase

AC Line Filter

Input Fusing

M1

Contactor