Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

125

Connecting the Kinetix 6000 Drive System

Chapter 5

External Shunt Module
Connections

Follow these guidelines when wiring your external active or passive shunt
module.

Figure 69 - Shunt Module Wiring

Figure 70 - Shunt Module Jumper Settings

(1) These are the default jumper settings.

IMPORTANT

When tightening screws to secure the wires, refer to the tables beginning on

page 95

for torque values.

IMPORTANT

To improve system performance, run wires and cables in the wireways as
established in

Chapter 2

.

Use This
Shunt Module

Cat. No.

With This
Drive Module

Do This

Power rail mounted shunt
module.

2094-BSP2

N/A

Verify the internal shunt jumper is in place between RC-2 and RC-3 (refer to

Figure 70

).

Verify the thermal switch jumper is in place between TS-1 and TS-2 (refer to

Figure 70

).

External passive shunt
module connected to the
power rail shunt module.

1394-SRxxxx

2094-BSP2
Shunt module

Remove the internal shunt jumper between RC-2 and RC-3.
Remove the thermal switch jumper between TS-1 and TS-2

(if your shunt module includes a thermal switch).

Refer to External Shunt Modules on

page 48

for noise zone considerations.

Refer to Shunt Module Wiring Examples on

page 195

.

Refer to the installation instructions provided with your Bulletin 1394 shunt module,

publication

2090-IN004

.

1 2 3

1 2

1 2 3

1 2

COL

INT

DC+

TS2
TS1

COL
INT
DC+

TS2
TS1

External Shunt Resistor

(RC) Connector

Kinetix 6000 Shunt Module, Top View

(catalog number 2094-BSP2)

External Thermal Switch

(TS) Connector

Cable Shield
Clamp

Jumpers

(1)