Circuit Breaker and Fuse Specifications

While circuit breakers offer some convenience, there are limitations for their use.
Circuit breakers do not handle high current inrush as well as fuses.

Make sure the selected components are properly coordinated and meet
acceptable codes including any requirements for branch circuit protection.
Evaluation of the short-circuit available current is critical and must be kept below
the short-circuit current rating of the circuit breaker.

The following fuse examples and Allen-Bradley® circuit breakers are
recommended for use with 2094-

xCxx-Mxx-S IAM modules when the Line

Interface Module (LIM) is not used.

Table 9 - Kinetix 6000 Circuit Breaker and Fuse Selection

Refer to the Kinetix Servo Drives Technical Data, publication

GMC-TD003

, for

additional power specifications for your IAM module.

IMPORTANT

LIM Modules (catalog numbers 2094-ALxxS, 2094-BLxxS, and 2094-XL75S-Cx) provide branch circuit protection to the IAM
module. Follow all applicable NEC and local codes.

IAM Module
Cat. No.

V AC Input Power

Control Input Power

DC Common Bus Fuse

Bussmann
Fuse

Allen-Bradley Circuit Breaker

Bussmann Fuse

(1)

Allen-Bradley

(2)

Circuit Breaker

Bussmann
Fuse

Ferraz Shawmut
Fuse

Disconnect

Magnetic
Contactor

2094-AC05-MP5-S

KTK-R-20 (20 A)

1492-SP3D300

140M-F8E-C16

FNQ-R-10 (10 A)

1492-SP2D060

N/A

A50P20-1

2094-AC05-M01-S

2094-AC09-M02-S

KTK-R-30 (30 A)

1492-SP3D400

140M-F8E-C20

FWH-35B

A50P35-4

2094-AC16-M03-S

LPJ-45SP (45 A)

N/A

140U-H6C3-C50

1492-SP2D200

FWH-60B

A50P60-4

2094-AC32-M05-S

LPJ-80SP (80 A)

N/A

140U-H6C3-C90

FWH-125B

A50P125-4

2094-BC01-MP5-S

KTK-R-20 (20 A)

1492-SP3D300

140M-F8E-C32

FNQ-R-10 (10 A) or
FNQ-R-7.5 (7.5 A)

1492-SP2D060 or
1492-SP1D150

FWJ-20A14F

DCT20-2

2094-BC01-M01-S

2094-BC02-M02-S

KTK-R-30 (30 A)

1492-SP3D400

140M-F8E-C45

FWJ-40A

A70QS40-4

2094-BC04-M03-S

LPJ-45SP (45 A)

N/A

140U-H6C3-C50

FWJ-70A

A70QS70-4

2094-BC07-M05-S

LPJ-80SP (80 A)

140U-H6C3-C90

FWJ-125A

A70QS125-4

(1) Use FNQ-R-7.5 fuse for higher single-cycle inrush current capability. This is recommended when the continuous control power current exceeds 3.0 A.
(2) Use 1492-SP1D150 circuit breaker for higher single-cycle inrush current capability. This is recommended when the continuous control power current exceeds 3.0 A.