Appendix C

DC Common Bus Applications

Calculate Total Bus
Capacitance

Total bus capacitance is the sum of all capacitance values for your Bulletin 2094
common-bus modules. Specifically, this includes the capacitance values for each
of these modules:

Leader IAM (converter and inverter) module
Each AM and shunt module (if present) on the leader IAM power rail
Each IPIM module (if present) on the leader IAM power rail
Each follower IAM (converter and inverter) module
Each AM module on the follower IAM power rail
Each IPIM module (if present) on the follower IAM power rail

Refer to Bulletin 2094 Drive Capacitance Values on

page 227

for IAM, AM,

IPIM, and shunt module capacitance values.

Table 116 - Maximum IAM Module Bus Capacitance

IMPORTANT

If total bus capacitance of your system exceeds the leader IAM module pre-
charge rating and input power is applied, the IAM module seven-segment
status indicator displays error code E90 (pre-charge timeout fault).

To correct this condition, you must replace the leader IAM module with a larger
module or decrease the total bus capacitance by removing AM modules or IPIM
modules.

Leader IAM (200V-class)
Module

Bus Capacitance,
max
μF

Leader IAM (400V-class)
Modules

Bus Capacitance,
max
μF

2094-AC05-MP5-x

7145

2094-BC01-MP5-x

4585

2094-AC05-M01-x

2094-BC01-M01-x

2094-AC09-M02-x

15,295

2094-BC02-M02-x

8955

2094-AC16-M03-x

34,400

2094-BC04-M03-x

8955

2094-AC32-M05-x

62,825

2094-BC07-M05-x

17,915

IMPORTANT

If your total bus capacitance value exceeds the value in the table above, you
must increase the size of the leader IAM module or decrease the total bus
capacitance by removing other modules on the power rail.