Connecting the Kinetix 6000 Drive System

Chapter 5

Ungrounded and High-impedance Grounded Power Configurations

Ungrounded and high-impedance grounded power configurations are allowed,
but you must jumper across a 120 k

Ω resistor (internal to the IAM module). The

ungrounded power configuration (shown below) does not provide a neutral
ground point. The IAM module has a ground jumper set for grounded power
distribution (default configuration).

Figure 41 - Ungrounded Power Configuration

Refer to Appendix A on

page 187

, for input-power interconnect diagrams with

and without the LIM module.

IMPORTANT

If you determine that you have ungrounded or high-impedance grounded
power distribution in your facility, you need to move the default jumper
(configured for grounded power) to the ungrounded power position inside the
IAM module.

Refer to Setting the Ground Jumper in Ungrounded Power Configurations on

page 87

for more information.

L3

L2

L1

DC-

DC+

L3

L2

L1

CONT EN-

CONT EN+

W

V

U

MBRK -

MBRK +

COM

PWR

DBRK -

DBRK +

CTRL 2

CTRL 1

1 2 3 4

1 2 3 4 5 6

1 2

1 2 3 4 5 6

1 2

1 2 3 4 5 6 7 8 9

BAUD

RATE

TX

RX

DPI

Transformer

Kinetix 6000 IAM Module,

Top View

Three-phase

Input VAC

Chassis Ground

Bonded Cabinet

Ground

Ground Grid or
Power Distribution Ground

Connect to power rail
ground stud.

Input Fusing

M1

Contactor

ATTENTION: Ungrounded systems do not reference each phase potential to a
power distribution ground. This can result in an unknown potential to earth
ground.