Connecting the Kinetix 6000 Drive System

Chapter 5

Power Wiring Guidelines

Use these guidelines as a reference when wiring the power connectors on your
IAM and AM drive modules.

For IPIM module power wiring guidelines, refer to the Kinetix 6000M
Integrated Drive-Motor System User Manual, publication

2094-UM003

.

Follow these steps when wiring the connectors on your IAM and AM drive
modules.

1. Prepare the wires for attachment to each connector plug by removing

insulation equal to the recommended strip length.

2. Route the cable/wires to your IAM and AM drive modules.
3. Insert wires into connector plugs.

Refer to connector pinout tables in

Chapter 4

or the interconnect

diagrams in

Appendix A

.

4. Tighten the connector screws.
5. Gently pull on each wire to make sure it does not come out of its terminal;

reinsert and tighten any loose wires.

6. Insert the connector plug into the module connector.

IMPORTANT

For connector locations of the Kinetix 6000 drive modules, refer to 2094 IAM/
AM Module Connector Data on

page 58

.

When tightening screws to secure the wires, refer to the tables beginning on

page 95

for torque values.

When removing insulation from wires, refer to the tables beginning on

page 95

for strip lengths.

IMPORTANT

To improve system performance, run wires and cables in the wireways as
established in Establishing Noise Zones on

page 37

.

IMPORTANT

Use caution not to nick, cut, or otherwise damage strands as you
remove the insulation.