Chapter 7

Troubleshooting the Kinetix 6000 Drive System

IAM/AM Module Status Indicators

Table 100 - Drive Status Indicator

Table 101 - Comm Status Indicator

Table 102 - Bus Status Indicator

Drive Status Indicator

Drive Status

Possible Resolution

Off

Normal, no faults

N/A

Steady red

Drive faulted

Refer to seven-segment error code and Kinetix 6000
Drive System Error Codes t
roubleshooting on

page 165

.

Comm Status Indicator

Drive Status

Potential Cause

Possible Resolution

Off

No communication

(1)

Loose fiber-optic connection.

Verify proper fiber-optic cable connections.

Broken fiber-optic cable.

Replace fiber-optic cable.

Receive fiber-optic cable connected to sercos transmit
connector and vice versa.

Check proper sercos fiber-optic cable connections.

Flashing green

Establishing communication

System is still in the process of establishing sercos
communication.

Wait for steady green indicator.

Node address setting on the drive module does not
match sercos controller configuration.

Verify proper node switch setting.

Steady green

Communication ready

No faults or failures.

N/A

(1) Refer to Fiber-optic Cable Installation and Handling Instructions, publication

2090-IN010

, for more information.

Bus Status Indicator

Bus Status

Condition

Off

No power or DC bus is not present.

Normal when bus power is not applied.
Fault exists, refer to seven-segment error code and Kinetix 6000 Drive System Error Codes

troubleshooting on

page 165

.

Bus power is present in follower IAM.

Follower IAM module is not configured as CommonBus Follow in the Logix Designer application.
After DC bus voltage is applied, a 2.5 second delay before the indicator begins flashing green is

normal operation to provide the common-bus leader module time to complete pre-charge.

Flashing green

Bus power is present, axis disabled.
No faults.

Normal when:
24V is not applied to Hardware Enable Input (IOD-2).
MSO instruction is not commanded in the Logix Designer application.

Steady green

Bus power is present, axis enabled.
No faults.

Normal when:
24V is applied to Hardware Enable Input (IOD-2).
MSO instruction is commanded in the Logix Designer application.