Change Parameters with the HIM Module

When using the HIM module to monitor or change parameters, use the up and
down arrows (

∧ and ∨) to arrive at selections. Refer to the instructions that came

with your HIM module for more information.

Follow these steps to monitor or change parameters with the HIM module.

1. Select parameter, and press

.

2. Select I/O AM1 Group (for IAM module), and press

.

3. Select Analog Outputs, and press

.

a. Analog Output 1 is displayed, and press

.

b. For Analog Output 2 use arrows to select, and press

.

4. Press Sel.
5. Enter parameter number, and press

.

Monitor System Variables with Analog Test Points

There are two analog output test points accessible from the IOD 26-pin
connector on the IAM and AM module.

Table 96 - IAM/AM I/O 26-pin (IOD) Connector

Figure 85 - Pin Orientation for 26-pin I/O (IOD) Connector

Refer to Analog Outputs on

page 69

for signal specifications.

IOD Pin

Description

Signal

23

Analog output 0

DAC0

24

Analog output common

DAC_COM

25

Analog output 1

DAC1

26

Analog output common

DAC_COM

Pin 18

Pin 26

Pin 1

Pin 9

Pin 10

Pin 19

26-pin IAM/AM

I/O Connector