Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

15

Chapter

1

Start

Use this chapter to become familiar with the design and installation requirements
for Kinetix 6000 drive systems.

IAM/AM Module Series
Changes

Series B drives included the peak current enhancement and applied to only the
460V (series A) IAM and AM modules. The peak current ratings of the
Kinetix 6000 (460V) drives are configured at the factory as 150% of continuous
current. However, you can program 460V AM modules and the equivalent IAM
(inverter) modules, for up to 250% of continuous inverter current.

Table 2 - Kinetix 6000 Enhanced Peak Performance Series Change

In series C drives, a mechanical relay for the brake circuit and another for the safe
torque-off inputs are replaced by solid-state relays and apply to the 230V
(series A) and 460V (series B) IAM and AM modules. All wiring is consistent
with previous series releases.

Topic

Page

IAM/AM Module Series Changes

15

About the Kinetix 6000 Drive Systems

16

Typical Hardware Configurations

17

Typical Communication Configurations

21

Catalog Number Explanation

22

Kinetix Drive Component Compatibility

23

Kinetix 6000M Integrated Drive-Motor System Compatibility

23

Agency Compliance

24

IAM Module
Cat. No.

AM Module
Cat. No.

Peak Current Rating

Series A (inverter)

Series B and C (inverter)

2094-BC01-MP5-S

2094-BMP5-S

150%

250%

2094-BC01-M01-S

2094-BM01-S

150%

250%

2094-BC02-M02-S

2094-BM02-S

150%

250%

2094-BC04-M03-S

2094-BM03-S

150%

250%

2094-BC07-M05-S

2094-BM05-S

150%

200%

IMPORTANT

Before your drive can deliver enhanced peak performance, you must enable the peak enhancement feature by configuring your
drive with DriveExplorer™ software or the Logix Designer application.

Refer to

Appendix F

on

page 255

to recalculate torque and acceleration or deceleration limit values, and paste them into the

appropriate Axis Properties dialog box in the Logix Designer application.

For more information on setting axis properties, refer to Configure Axis Properties on

page 149

.