Enhanced Peak Performance

Appendix F

Enhanced Peak Example

In this example, the following motor and drive combination is used:

Drive = 2094-BC02-M02-S
Motor = MPL-B540K

Table 129 - Example Definitions

Figure 120 - Example Torque Formula

1. Navigate to Axis Properties and click the Limits tab.

2. Overwrite the existing Peak Torque Limit (TorqueLimitBipolar) value.

In this example, the calculated value is 178.1.

3. Click Set Custom Limits.

Description

Symbol

IDN

Example

Motor continuous current (A

rms

)

I

mtr, cont

S:0:0111

14.49525

Motor peak current (A

rms

)

I

mtr, pk

S:0:0109

42.42641

Drive continuous current (A

rms

)

I

dr, cont

S:0:0112

10.3379

Drive peak current (A

rms

)

I

dr, pk

S:0:0110

150%: 15.5069

250%: 25.8094

Torque

max

mtr, pk

min (I

, I )

dr, pk

=

=

mtr, cont

I

rms

min (42.4 A

, 25.8 A )

rms

= 178.1%

14.5 A

rms

Default Peak Torque Limit Value

Default TorqueLimit Values