6

Error messages

110

Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

PROFIsafe has left data exchange [0x012f0025]

PROFIsafe - invalid data [0x012f0026]

F-parameter error [0x012f0027]

Discrepancy error or functional test SD-In1 [0x012f0031]

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

37

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

A fault has occurred in the PROFIsafe data processing.

PROFIsafe has left data exchange.

• Check communication module, bus connection and

control program.

• Read out fault memory of control system.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

38

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

A fault has occurred in the PROFIsafe data processing.

PROFIsafe user data area has no valid data.

• Check communication module, bus connection and

control program.

• Read out fault memory of control system.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

39

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

A fault has occurred in the PROFIsafe parameterisation

phase. Wrong parameterisation of F-PLC.

• Check communication module, bus connection and

control program.

• Read out fault memory of control system.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

49

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Signal error at two-channel safe input SD-In1.

• Check safe parameters for SD-In1.

• Check sensor at SD-In1.

Advertising