F_dest_add unequal f address [0x012f0040, F_dest_add = 0 or ffffhex [0x012f0041, F_source_add = 0 or ffffhex [0x012f0042 – Lenze E94AYAE SM301 User Manual

Page 113: F_wd_time is 0 msec [0x012f0043, F_sil exceeds technical sil [0x012f0044, 0x012f0041, 0x012f0040, 0x012f0044, 0x012f0042, 0x012f0043

Advertising
background image

Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

113

6

Error messages

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

F_Dest_Add unequal F address [0x012f0040]

F_Dest_Add = 0 or FFFFhex [0x012f0041]

F_Source_Add = 0 or FFFFhex [0x012f0042]

F_WD_Time is 0 msec [0x012f0043]

F_SIL exceeds technical SIL [0x012f0044]

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

64

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The safety address F_Dest_Add of the control system

does not correspond to the F address in the safety

module.

Adapt the safety address in the control configuration to

the address in the safety module.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

65

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The safety address F_Dest_Add in the control system is

invalid (0 or FFFF

hex

).

Select a valid value for the safety address data in the

control configuration.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

66

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The safety address F_Source_Add in the control system is

invalid (0 or FFFF

hex

).

Select a valid value for the safety address data in the

control configuration.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

67

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The monitoring time F_WD_Time of the control system is

set to 0 ms.

Select a permissible value for the monitoring time

F_WD_Time.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

68

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The parameterised SIL setting in the control system

exceeds the technically possible SIL of the safety module.

Adapt the parameterised SIL setting in the control

system to the safety module used.