Ss1/ss2: speed ramp exceeded [0x012f006e, Sli: safely limited increment exceeded [0x012f006f, Stuck at high sd-out1, channel a [0x012f0080 – Lenze E94AYAE SM301 User Manual

Page 119: Stuck at low sd-out1, channel a [0x012f0081, 0x012f006f, 0x012f006e, 0x012f0080, 0x012f0081, 6error messages

Advertising
background image

Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

119

6

Error messages

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

SS1/SS2: Speed ramp exceeded [0x012f006e]

SLI: Safely limited increment exceeded [0x012f006f]

Stuck at High SD-Out1, channel A [0x012f0080]

Stuck at Low SD-Out1, channel A [0x012f0081]

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

110

Response (Lenze setting printed in bold)

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The monitoring of the speed ramp is activated. When the

SS1/SS2 stop function is executed, the deceleration of

the speed ramp is monitored. If the monitoring limits are

exceeded, an error is reported.

• Adapt ramp monitoring parameters in the safety

module.

• Adapt (quickstop) ramp parameters in the

application.

• Deactivate ramp monitoring in the safety module.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

111

Response (Lenze setting printed in bold)

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The safely limited increment is monitored in the "special

operation" operating mode. The increment

parameterised was exceeded.

• Adapt "SLI: Safely limited increment" parameter.

• Limit increments in the application.

• Deactivate monitoring of the safely limited

increment.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

128

Response (Lenze setting printed in bold)

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Channel A of output SD-Out1 cannot be deactivated.

Check wiring at the output SD-Out1 for short circuit.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

129

Response (Lenze setting printed in bold)

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Channel A of output SD-Out1 cannot be activated.

Check supply voltage and wiring for the safe output.

Advertising