5.1

Parameter list | C15501

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C15501

C15502

C15800

Parameter | Name:

C15501 | Position encoder gearbox factor

Data type: UNSIGNED_16

Index: 9074

d

= 2372

h

From V1.3

Setting of the gearbox factor between motor and position encoder.

Safe speed measurement and position detection

Setting range

(min. value | unit | max. value)

Lenze setting

20

%

50000 100 %

Read access  Write access  CINH  PLC-STOP  No transfer Scaling factor: 1

Parameter | Name:

C15502 | Position encoder mounting direction

Data type: UNSIGNED_8

Index: 9073

d

= 2371

h

From V1.3

Setting of the mounting direction of the position encoder referred to the motor encoder.

Safe speed measurement and position detection

Selection list

(Lenze setting printed in bold)

0 Like motor encoder
1 Inverse to motor encoder

Read access  Write access  CINH  PLC-STOP  No transfer Scaling factor: 1

Parameter | Name:

C15800 | Current error type

Data type: UNSIGNED_8

Index: 8775

d

= 2247

h

Type of the currently pending error.
Selection list

(read only)

0 No error
1 Warning
2 Trouble

Read access  Write access  CINH  PLC-STOP  No transfer Scaling factor: 1