1 required settings in the controller, Required settings in the controller, 2introduction – Lenze E94AYAE SM301 User Manual

Page 16

Advertising
background image

2

Introduction

2.5

Parameter setting & configuration

16

Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

2.5.1

Required settings in the controller

The safety module expected by the application and the controller is selected in

C00214

.

• In »Engineer« this setting is carried out automatically by assigning the device modules to the

controller, i.e. »Engineer« automatically sets

C00214

according to the safety module selected.

• If the safety module set in

C00214

does not comply to the plugged-in safety module type, an

error (fault) is triggered. The error can only be eliminated by mains switching.

Note!

When communicating online via a bus system it may happen that several users access

one and the same drive at the same time and edit the safe parameter set.
After transferring the safe parameters, it must be checked whether the check sums (CRC)

of the parameter set, memory module, and the safety module comply to each other in

the Safe Transfer dialog box.
Since safe parameter access through several users cannot be technically avoided at

present, organisational measures are required to ensure the consistency of the safe

parameters.

Parameter | Name:

C00214 | Required safety module

Data type: UNSIGNED_8

Index: 24361

d

= 5F29

h

Setting of the expected safety module
Selection list

1 SM0
2 SM100
4 SM300
5 SM301

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT