2 case study 2: "signalling, Case study 2: "signalling, 3safe configuration – Lenze E94AYAE SM301 User Manual

Page 40

Advertising
background image

3

Safe configuration

3.8

Safe output

40

Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.8.2

Case study 2: "Signalling"

Switching condition
The following switching condition is to be implemented for the safe output SD-Out1:

• Safe signalling is carried out (SD-Out1 in ON state) if

• the power supply for the motor is safely interrupted (STO active)
AND NO error is active (Error active).

[3-2]

Logic operation for case study "Signalling"

Required parameter setting for SD-Out1

1. Set the following switching condition to "Positive logic":

• STO is active

2. Set the following switching condition to "Negative logic":

• Fault active

3. Set all other switching conditions to "Not evaluated".
4. Set logic function to "AND".
5. If a safety bus has been parameterised:

• The "SD-Out1" bit of the safety control is considered in the ANDing.
• Hide the "SD-Out1" bit via the "S bus: Filter control data" parameter to suppress this access.

SD-Out1 in ON state

STO active

Error active

&