Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

57

3

Safe configuration

3.9

Safety functions

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.9.4

Cascading (CAS)

From SM301 V1.1

Tip!
Detailed information on cascade wiring can be found in the manual for the safety module.

Cascading / CAS
Description

This function enables the synchronised shutdown of an entire drive system.

• The function can only be activated via parameter setting. See parameter "CAS: Cascading".

• When the function is active:

• The safe SD-In4 input is used as a cascading input and can no longer be used as universal

input.

• The safe SD-Out1 output is used as a cascading output and can no longer be parameterised

as universal feedback output.

• An emergency stop function (SSE) tripped by cascading cannot be overridden by the

Enable

switch (ES)

during special operation.

• The cascade triggers with every

STO

, independently of which safety module has the STO

status and for what reason.

• All safety modules of the cascade can only be enabled if all cascading inputs (SD-In4) are in

the OFF state.

Preconditions

• The SD-In4 input must be parameterised as an active input for the "emergency stop" function

and the input delay for SD-In4 must be ≤ 10 ms.

Safe inputs ( 34)

• Via the "SSE: Emergency stop function" parameter,

STO

must be parameterised as the

emergency stop function to be executed.

Emergency stop function (SSE) ( 44)

• The restart behaviour following the execution of the

STO

/

SS1

stop function must be

parameterised to "acknowledged restart".

Restart behaviour ( 43)

• The control of the SD-Out1 output via a parameterised safety bus must be inhibited.

Safety

bus ( 59)

• The plausibility check rejects other settings until you have parameterised them correctly.

• In the cascade connection, you can only change from the

SS2

/SOS stop function to the

confirmation during special operation. The

STO

/

SS1

stop function would always trigger the

interconnection and a confirmation would thus not be possible.

Principle

Parameter

C15035

CAS: Cascading

C15036

CAS: Stop delay

• Display of the time that passes between switching of the SD-Out1 output

to the OFF state and the detection of the OFF state at the SD-In4 input.

This information can be helpful when commissioning/maintaining the

system.

• If "0 ms" is displayed after a stop, another safety module has triggered

the stop via the cascade.

• The time that passes until the next system acknowledgement is

displayed.

Activate

How to activate the function:

• Set "CAS: Cascading" parameter to "cascading with SD-In4".

SD-Out1

SD-In4

SM301 #1

SM301 #2

SD-In4

SD-Out1

SM301 #n

SD-In4

SD-Out1