Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

45

3

Safe configuration

3.9

Safety functions

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.9.1.5

Safe stop 1 (SS1)

Safe Stop 1 / SS1 (corresponds to a "Stop1" according to EN 60204)
Description

The safety module monitors whether the drive has reached the set tolerance margin (n=0)

within the parameterised stopping time and, depending on the parameterised SS1 mode, after

the stopping time has elapsed or after falling below the tolerance margin (n=0), switches the

drive to torque-free operation via the

STO

safety function.

From SM301 V1.4

additionally the deceleration ramp for the SS1 stop function can be

parameterised and monitored.

Ramp monitoring (SS1/SS2) ( 48)

• The drive must be braked to standstill through the application!

• The speed is calculated from the encoder data.

Safe speed measurement and position

detection ( 31)

• In SS1 mode "STO with n=0", you can use the parameter "STO delay after n=0" to set a waiting

time which determines when the

STO

status is adopted.

• Without an encoder, the function evaluates the speed status n=0 of the controller. In this

case the stopping time monitored by the safety module must be 0.5 s longer than the

stopping time parameterised on the controller.

• Additional measures are required against movements caused by external forces, e.g.

mechanical brakes. The application time of a brake must be considered when determining

the stopping time.

• A restart is only possible after the stopping time has elapsed completely. This does not apply

to special operation.

Restart behaviour ( 43)

Priority

Priority function:

STO

Subordinated function:

SS2

Function

From SM301 V1.3, function  (STO with n=0) can be selected as SS1 mode.

Parameter

C15306

SS1 mode:
 STO after stopping time

 STO with n=0

C15305

SS1, SS2: Stopping time

C15307

SS1: STO delay after n=0

C15310

Speed window (n=0)

Activation

How to activate the function:

• A data telegram with a corresponding content is sent to the controller via the safety bus.

Safety bus ( 59)

• "OFF state" at a safe input which has been assigned to the function by parameter setting.

Safe inputs ( 34)

• As response to the error stop request.

• As response to the emergency stop request.

Normal

behaviour

When the stopping time has elapsed or after falling below the tolerance margin (n=0), a

standard stop is activated.

• The power supply for the motor is safely interrupted immediately (

STO

). The motor cannot

generate a torque and thus no dangerous movements of the drive.

Error behaviour

If standstill has not been reached when the stopping time has elapsed, or if the deceleration

ramp parameterised was exceeded during the

Ramp monitoring

was activated, an error

message is triggered and an error stop is activated.

• The power supply for the motor is safely interrupted immediately (

STO

). The motor cannot

generate a torque and thus no dangerous movements of the drive.

n

t

0

STO

Ž

STO

n

t

0

SS1

STO

Œ

Ž

STO

SS1



Œ

0

1