4 compatibility mode, Compatibility mode, 3safe configuration – Lenze E94AYAE SM301 User Manual

Page 28

Advertising
background image

3

Safe configuration

3.4

Compatibility mode

28

Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.4

Compatibility mode

The functional range of the SM301 safety module which can be parameterised in the »Engineer« via

the Safe configuration tab depends on the version of the safety module selected for the controller

via the Insert device module dialog box.
Existing projects created e.g. with an SM301 V1.0 safety module can also be downloaded into a

controller with a plugged-in SM301 V1.1 safety module. In this example, the functional range which

can be parameterised via the Safe configuration tab corresponds to the one of the SM301 V1.0

safety module (V1.0 compatibility mode).

Tip!

C15016

displays the parameter set version of the safety module.

3.5

Protection of the safe parameters by project-related password entry

This function is available from »Engineer« HighLevel V2.14!

The »Engineer« provides a password protection which serves to protect the parameter setting of the

higher-order safety functions from alterations in the project for the device series 8400 and 9400.
The password...

• ...can be set on the Protection tab when the project root element has been selected in the project

tree.

• ...is only valid inside the project (no transmission to the controller or safety module). If a

password is stored in the project and this project is used, the safe parameters can only be edited

after the password has been entered.

How to activate the protection of the save parameters:

1. Select the project root element in the

project tree.

2. Assign the desired password on the Protection tab.

• After the password has been set, the safe parameters (tab Safe configuration, safe

parameters) of all included devices can only be edited inside the project after the

corresponding password has been entered.