2.5.2.3

Control information

Via the bit-coded control signal SMI_dwControl of the SB LS_SafetyModuleInterface the SM301

safety module transmits information about requested/active safety functions to the application.

• Several safety functions can be requested/active at the same time.

Bit coding of the SMI_dwControl status signal

Bit

Name

Meaning

1 SS1 active

Safe stop 1 (SS1)

function is active.

• After the parameterised stopping time has elapsed, bit 0 of the status signal

SMI_dnState (STO active) is set.

2 SS2 active

Safe stop 2 (SS2)

function is active.

• After the parameterised stopping time has elapsed, bit 16 (SOS monitored) is set.

3 SLS1 active

Safely limited speed 1 (SLS1)

function is active.

• After the parameterised braking time Nlim1 has elapsed, bit 8 of the status signal

SMI_dnState (SLS1 monitored) is set additionally.

4 SLS2 active

*

Safely limited speed 2 (SLS2)

function is active.

• After the parameterised braking time Nlim2 has elapsed, bit 9 of the status signal

SMI_dnState (SLS2 monitored) is set additionally.

5 SLS3 active

*

Safely limited speed 3 (SLS3)

function is active.

• After the parameterised braking time Nlim3 has elapsed, bit 10 of the status

signal SMI_dnState (SLS3 monitored) is set additionally.

6 SLS4 active

*

Safely limited speed 4 (SLS4)

function is active.

• After the parameterised braking time Nlim4 has elapsed, bit 11 of the status

signal SMI_dnState (SLS4 monitored) is set additionally.

7 SDIpos active

**

Function

Safe positive direction (SDIpos)

is active.

• After the parameterised SDI delay time has elapsed, bit 12 of the status signal

SMI_dnState (SDIpos monitored) is set additionally.

8 SDIneg active

**

Function

Safe negative direction (SDIneg)

is active.

• After the parameterised SDI delay time has elapsed, bit 13 of the status signal

SMI_dnState (SDIneg monitored) is set additionally.

9 ES active

Enable switch (ES)

function for motion functions in special operation is active.

10 SLI is active

***

"Safely limited increment (SLI)" function is active.

11 OMS

Operation mode selector (OMS)

function for special operation is requested.

16 SOS active

"Safe operating stop" (SOS) function is active.

• The safe operating stop is monitored.

• The function will be active after the function

Safe stop 2 (SS2)

has ended.

23 SSE active

Emergency stop function (SSE)

is active.

• Depending on the parameterisation of the emergency stop function, bit 1 (SS1

active) or bit 0 of the status signal SMI_dnState (STO active) is set after the

function has ended.

29 OMS active

*

Special operation is active.

* From SM301 V1.1 ** From SM301 V1.3 *** From SM301 V1.4

Bits not listed are reserved for future extensions!

Note!

To effect the corresponding action (e.g. braking to standstill, holding the standstill

position), the application engineer has to provide an appropriate interconnection in the

application.

• To integrate the basic function "Limiter", the output SMI_dwControl is to be

connected to the input LIM_dwControl of the LS_Limiter system block.