3 operation mode selection, 1 operation mode selector (oms), Operation mode selection – Lenze E94AYAE SM301 User Manual

Page 54: Operation mode selector (oms), 3safe configuration

Advertising
background image

3

Safe configuration

3.9

Safety functions

54

Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.9.3

Operation mode selection

Short overview of "Safety functions Operation mode selection" parameter group:

3.9.3.1

Operation mode selector (OMS)

Parameter

Info

Lenze setting

Value Unit

C15200

OMS: Stop function

STO

C15201

OMS: Motion function

SLS1

C15202

OMS: Function at LOW level

*

Normal operation

C15203

Safely limited increment

**

1 Incr.

* From SM301 V1.3 ** From SM301 V1.4

Operation Mode Selector / OMS
Description

This function serves to switch between normal operation and "special operation" of the drive.

• Special operation enables the overriding of a standard stop (

STO

,

SS1

and

SS2

) by release

through the enable switch.

Enable switch (ES) ( 56)

From SM301 V1.4:

The monitoring function of the safely limited increment is active as soon

as a value > 0 has been entered in

C15203

. The setting "0" deactivates the SLI monitoring

function.

• The monitoring function parameterised is automatically activated with the transition to

special operation. A motion function other than "traverse freely" at the same time is

monitoring function in special operation.

OMS: Function at LOW level

If the operation mode selector is implemented via a safe input, the operating mode for the LOW

level is to be selected with care

(from SM301 V1.3)

.

According to the closed-circuit principle, no additional danger must be caused by normal or

special operation in the corresponding application.

For detailed information, please see the manual for the safety module.

Preconditions

• A safe input must be parameterised and interconnected as an operation mode selector. You

can only connect and parameterise one operation mode selector. The OMS bit of the safety

bus must be deactivated (

C15113

). When a safe input is used, the LOW level function must

be set depending on the application

(from SM301 V1.3)

.

• Special operation can also be selected via the safety bus with the OMS bit unless a safety

input is set as an operation mode selector.

• The plausibility check rejects ambiguous settings until you have parameterised them

correctly.