Sos: tolerance limit exceeded [0x012f006a, No encoder system configured [0x012f006b, Cas: circulation time exceeded [0x012f006c – Lenze E94AYAE SM301 User Manual

Page 118: Cas: hardware or discrepancy error [0x012f006d, 0x012f006c, 0x012f006d, 0x012f006b, 0x012f006a, 6error messages

Advertising
background image

6

Error messages

118

Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

SOS: Tolerance limit exceeded [0x012f006a]

No encoder system configured [0x012f006b]

CAS: Circulation time exceeded [0x012f006c]

CAS: Hardware or discrepancy error [0x012f006d]

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

106

Response (Lenze setting printed in bold)

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The drive has exceeded a tolerance limit for the SOS

function.

• Adapt tolerance limits or increase distance to the

parameterised limits.

• Adapt response time of encoder monitoring.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

107

Response (Lenze setting printed in bold)

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

A speed- or position-based safety function is tried to be

carried out without an encoder having been configured.

Configuration of an encoder system valid for safety-

related applications.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

108

Response (Lenze setting printed in bold)

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The maximum time between the activation and

feedback of cascading has been exceeded.

• Input delay for SD-In4 must be parameterised lower

than or equal to 10 ms.

• Check wiring between the cascaded modules.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

109

Response (Lenze setting printed in bold)

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The cascading output has not been deactivated by the

hardware quickly enough, or there is a discrepancy at the

cascading input.

• Check wiring between the cascaded modules.

• Replace safety module.