Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

39

3

Safe configuration

3.8

Safe output

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Tip!

• Case studies with regard to the parameter setting of the safe output can be found in the

following subchapters.

•

C15060

displays the output image of the safety module.

3.8.1

Case study 1: "Safety door"

Switching condition
The following switching condition is to be implemented for the safe output SD-Out1:

• Opening the safety door is permitted (SD-Out1 in ON state) if

• the power supply for the motor is safely interrupted (STO active)
• OR special operation is active (OMS active)
• OR the safe operating stop is active and monitored (SOS monitored).

[3-1]

Logic operation for "Safety door" case study

Required parameter setting for SD-Out1

1. Set the following switching conditions to "Positive logic":

• STO is active
• OMS active
• SOS monitored

2. Set all other switching conditions to "Not evaluated".
3. Set logic function to "OR".
4. If a safety bus has been parameterised:

• The "SD-Out1" bit of the safety control is considered in the ORing.
• Hide the "SD-Out1" bit via the "S bus: Filter control data" parameter to suppress this access.

STO active

OMS active

SOS monitored

SD-Out1 in ON state

³1