Load initial configuration values chapter 7 – Rockwell Automation 1771-QDC, D17716.5.93(Passport) PLASTIC MOLDING MODULE User Manual

Page 100

Advertising
background image

Enter Your Values Here

Load Initial Configuration Values

Chapter 7

7-14

Worksheet 7ĆF (continued)
Plastication Configuration Block (PLC)

Control Word ProĆSet 600 Addr.

Value

Description

Units

PLC06

N44:362

1000

Minimum ERC PercentageĆĆPressure

Percent

8

PLC08

N44:364

0

Profile Watchdog Timer Preset

Time

1

PLC09

N44:365

*

Output #1 SetĆoutput Value During Profile

Percent Signal Output

4

PLC10

N44:366

*

Output #2 SetĆoutput Value During Profile

Percent Signal Output

4

PLC11

N44:367

*

Output #3 SetĆoutput Value During Profile

Percent Signal Output

4

PLC12

N44:368

*

Output #4 SetĆoutput Value During Profile

Percent Signal Output

4

PLC17

N44:373

0

Output #1 Acceleration Ramp Rate During Profile

Percent Signal Output per Second

5

PLC18

N44:374

0

Output #2 Acceleration Ramp Rate During Profile

Percent Signal Output per Second

5

PLC19

N44:375

0

Output #3 Acceleration Ramp Rate During Profile

Percent Signal Output per Second

5

PLC20

N44:376

0

Output #4 Acceleration Ramp Rate During Profile

Percent Signal Output per Second

5

PLC25

N44:381

0

Output #1 Deceleration Ramp Rate During Profile

Percent Signal Output per Second

5

PLC26

N44:382

0

Output #2 Deceleration Ramp Rate During Profile

Percent Signal Output per Second

5

PLC27

N44:383

0

Output #3 Deceleration Ramp Rate During Profile

Percent Signal Output per Second

5

PLC28

N44:384

0

Output #4 Deceleration Ramp Rate During Profile

Percent Signal Output per Second

5

PLC33

N44:389

*

Output #1 SetĆoutput Value at EndĆof Profile

Percent Signal Output

4

PLC34

N44:390

*

Output #2 SetĆoutput Value at EndĆof Profile

Percent Signal Output

4

PLC35

N44:391

*

Output #3 SetĆoutput Value at EndĆof Profile

Percent Signal Output

4

PLC36

N44:392

*

Output #4 SetĆoutput Value at EndĆof Profile

Percent Signal Output

4

PLC41

N44:397

0

Pressure Minimum Control Limit

Pressure

3

PLC42

N44:398

*

Pressure Maximum Control Limit

Pressure

3

PLC43

N44:399

*

Selected Pressure Valve, Output for Minimum

Percent Signal Output

4

PLC44

N44:400

*

Selected Pressure Valve, Output for Maximum

Percent Signal Output

4

PLC49

N44:405

100

Proportional Gain for Pressure Control

None

PLC50

N44:406

400

Integral Gain for Pressure Control

Inverse Time (Algorithm)

6

PLC51

N44:407

0

Derivative Gain for Pressure Control

Time (Algorithm)

7

PLC57

N44:413

0

Profile High Pressure Alarm Setpoint

Pressure

3

1

Time

3

Pressure

4

Percent Signal Output

00.00 to 99.99 seconds 0000 to 9999 PSI 00.00 to 99.99

000.0 to 999.9 Bar

5

Percent Signal Output per Second

6

Inverse Time (Algorithm)

7

Time (Algorithm)

8

Percent

0000 to 9999 00.00 to 99.99 Minutes (ISA) 00.00 to 99.99 Minutes (ISA) 00.00 to 99.99

00.00 to 99.99 Seconds (AĆB) 00.00 to 99.99 Seconds (AĆB)

* Refer to the appropriate section later in this chapter for information on this parameter