Tune Your Machine

Chapter 10

10-35

ERC is not required for repeatable clamp or ejector positioning. Without
ERC, the QDC module will still force the clamp or ejector to overshoot by
a constant repeatable amount (relative to cylinder speed and QDC
module’s 2 ms scan time).

Do NOT use ERC when:

spanning your valves
using velocity feedforward gain
using profile ramp rates to smooth the operation.
you have NOT tuned the machine in closed-loop control

ATTENTION: Jerky, abrupt clamp motion may result if you
apply ERC to a control loop that has not been properly tuned.

ERC Minimum Percentage Values
If using ERC, adjust values recommended in chapter 7 as follows:

If ERC is enabled (on) and:

Then:

The actual velocity or pressure swings wildly

around the setpoint from cycle to cycle

Decrease the ERC minimum % value

The actual velocity or pressure takes several

cycles to achieve the desired setpoint

Increase the ERC minimum % value