Chapter 9

9-14

To do this: change FCC44, download the FCC block, and repeat steps 1-3.
Repeat as necessary.

Important: If downloading from your programming terminal, download
FCC followed by CPC with download bits B21/2 and 6 (chapter 4).

4.

Copy final FCC44 (N43:40) into SCC44 and TCC44 (N43:100 and
160) and download these changes to the QDC module.

Important: If downloading from your programming terminal, download
FCC, SCC, TCC, and CPC in that order with download bits B21/2, 3, 4,
and 6 respectively (chapter 4).

What You Have Accomplished

The valve spanning procedure you just completed has defined the:

range of pressure available during first, second and third clamp close

end-of-range maximum and minimum signal levels for linear control of

the clamp close pressure valve in open-loop control.

For this

range limit

When trying to obtain

the pressure in:

The QDC module drives the selected

pressure valve to % output signal in:

Minimum

FCC41, SCC41, TCC41

FCC43, SCC43, TCC43

Maximum

FCC42, SCC42, TCC42

FCC44, SCC44, TCC44

Now for all open-loop clamp close pressure profiles, the QDC module
assumes a linear relationship between clamp pressure and signal output.

Set Profile Pressure Alarms

For clamp close profiles, set your maximum pressure alarms FCC57,
SCC57, and TCC57 (N43:53, 113, and 173) to a pressure that should:

not be exceeded during the clamp close profile
not exceed the maximum pressure control limit FCC42, SCC42, TCC42

Entering a value of zero disables this alarm.

Send new values to QDC module by downloading FCC, SCC, and TCC.

Important: If downloading from your programming terminal, download
FCC, SCC, TCC, and CPC in that order with download bits B21/2, 3, 4,
and 6 respectively (chapter 4).