Configure the qdc module's i/o chapter 3, Set up maximum pressure alarms and time delays – Rockwell Automation 1771-QDC, D17716.5.93(Passport) PLASTIC MOLDING MODULE User Manual

Page 60

Advertising
background image

Enter Your PressureĆalarm and TimeĆdelay Values Here

Configure the QDC Module's I/O

Chapter 3

3-16

Set Up Maximum Pressure Alarms and Time Delays

The QDC module continuously monitors the system pressure input. When
it detects that the process input equals or exceeds a preset alarm setpoint,
the QDC module sets an alarm bit. A setpoint of zero disables the
associated alarm.

To guard against nuisance alarms caused by noise spikes or pressure
transients, you can set a time delay so the QDC module must monitor
continuous excessive pressure for an amount of time before setting the
high pressure alarm. A setpoint of zero disables this delay.

Configure the QDC module for the system pressure alarm as follows:

1.

Determine these values:

pressure-alarm setpoint
time-delay setpoint

2.

Record non-zero setpoints on Worksheet 3-G for the pressure alarm
and time delay.

3.

Download them to the QDC module using the procedures presented
earlier in this chapter.

Worksheet 3ĆG

PressureĆalarm and TimeĆdelay Setpoints

Control Word

ProĆSet 600 Addr. Value

Description

MCC61

N40:57

System PressureĆalarm Setpoint

2

MCC62

N40:58

System Pressure TimeĆdelay Setpoint

1

1

Time Measured in Seconds

2

Pressure

00.00 to 00.99

0000 to 9999 PSI

000.0 to 999.9 Bar