Span Your Valves

Chapter 9

9-31

We recommend that you span your pack and hold pressure valves for
optimum pressure performance in four parts:

Confirm critical values
Span your pack and hold pressure valves
Test valve linearity with a pressure vs. time profile
Set profile pressure alarms

Important: You may omit the procedure Span your pack and hold pressure
valves
in this section if the recorded valve spanning data from the manu-
facturer in pressure control limits PKC41-44 and HDC41-44 (chapter 7) are
adequate for your application.

Important: If your machine hydraulics for pack and hold are identical to
those for injection, you may use your injection pressure valve spanning
parameters for pack and hold. If so, enter your values for INC41-44 into
PKC41-44 and into HDC41-44, and skip to Set Profile Pressure Alarms.

Confirm Critical Values

Important: Confirm that all entries you made for configuration values
(chapter 7) and profile values (chapter 8) are as follows:

On

Worksheet

Confirm Your Configuration

With These Words or Bits

for Pack Pressure

ProĆSet Addr

7ĆF

QDC module output to which you connected your

pressure control valve

PKC02ĆB06, B05, B04

B38/148Ć150

SetĆoutput values for unselected valves

PKC09Ć12 = your values

N44:125Ć128

All ramping is disabled with zero ramp rates

PKC17Ć20 = 0

PKC25Ć28 = 0

N44:133Ć136

N44:141Ć144

Pressure limits:

Minimum Pressure Control Limit

Maximum Pressure Control Limit

Selected Pressure Valve, Output for Minimum

Selected Pressure Valve, Output for Maximum

PKC41 = 0

PKC42 = system pressure

PKC43 = your value

PKC44 = your value

N44:157

N44:158

N44:159

N44:160

7ĆG

QDC module output to which you connected your

pressure control valve

HDC02ĆB06, B05, B04

B38/212Ć214

SetĆoutput values for unselected valves

HDC09Ć12 = your values

N44:185Ć188

All ramping is disabled with zero ramp rates

HDC17Ć20 = 0

HDC25Ć28 = 0

N44:193Ć196

N44:201Ć204

EndĆofĆprofile setĆoutput values

HDC33Ć36 for zero output

N44:209Ć212

Pressure limits:

Minimum Pressure Control Limit

Maximum Pressure Control Limit

Selected Pressure Valve, Output for Min

Selected Pressure Valve, Output for Max

HDC41 = 0

HDC42 = system pressure

HDC43 = your value

HDC44 = your value

N44:217

N44:218

N44:219

N44:220

PKC and HDC Profiles -

Pressure Valves