Load initial configuration values chapter 7 – Rockwell Automation 1771-QDC, D17716.5.93(Passport) PLASTIC MOLDING MODULE User Manual

Page 109

Advertising
background image

Load Initial Configuration Values

Chapter 7

7-23

Table 7.A

SetĆoutput Values for Unselected Valves

If the unselected

valve controls:

and the unselected

valve type is:

and during profile,

valve action is:

and during profile,

you require:

Then Enter:

Pressure

UniĆdirectional

Direct acting

Maximum Pressure 9999

Pressure

UniĆdirectional

Direct acting

Medium Pressure

7500 to 5000

Pressure

UniĆdirectional

Direct acting

Low Pressure

5000 to 2500

Pressure

UniĆdirectional

Direct acting

Minimum Pressure

0

Pressure

UniĆdirectional

Reverse acting

Maximum Pressure 0

Pressure

UniĆdirectional

Reverse acting

Medium Pressure

2500 to 5000

Pressure

UniĆdirectional

Reverse acting

Low Pressure

5000 to 7500

Pressure

UniĆdirectional

Reverse acting

Minimum Pressure

9999

Flow

UniĆdirectional

Direct acting

Maximum Flow

9999

Flow

UniĆdirectional

Direct acting

Medium Flow

7500 to 5000

Flow

UniĆdirectional

Direct acting

Low Flow

5000 to 2500

Flow

UniĆdirectional

Direct acting

Minimum Flow

0

Flow

UniĆdirectional

Reverse acting

Maximum Flow

0

Flow

UniĆdirectional

Reverse acting

Medium Flow

2500 to 5000

Flow

UniĆdirectional

Reverse acting

Low Flow

5000 to 7500

Flow

UniĆdirectional

Reverse acting

Minimum Flow

9999

Flow

BiĆdirectional

Direct acting

Maximum Flow

9999

Flow

BiĆdirectional

Direct acting

Medium Flow

8750 to 7500

Flow

BiĆdirectional

Direct acting

Low Flow

7500 to 6250

Flow

BiĆdirectional

Direct acting

Minimum Flow

5000

Flow

BiĆdirectional

Reverse acting

Maximum Flow

0

Flow

BiĆdirectional

Reverse acting

Medium Flow

1250 to 2500

Flow

BiĆdirectional

Reverse acting

Low Flow

2500 to 3750

Flow

BiĆdirectional

Reverse acting

Minimum Flow

5000

Record all set-output values for unselected valves on your worksheets.

Important: Valve spanning procedures in chapter 9 require unselected
valves be driven at signal levels representative of a normal production run.
We discuss process considerations that impend changing these values in
chapter 10. Changing these values may require you to re-span your valves.

Advertising