Span Your Valves

Chapter 9

9-10

Span your clamp close pressure valve(s) for optimum performance.
Do this in four parts:

Confirm critical values
Span your clamp close pressure valve(s)
Test valve linearity
Set pressure alarm setpoints

Important: You may omit the procedure Span your clamp close pressure
valve(s)
in this section if the recorded valve spanning data from the
manufacturer for pressure control limits FCC41-44, SCC41-44, and
TCC41-44 (chapter 7) are adequate for your application.

Confirm Critical Values

Important: Confirm that your entries for configuration values (chapter 7)
and profile values (chapter 8) for clamp close profiles are as follows:

On Worksheet: Confirm Your Configuration:

With These Words or Bits:

ProĆSet Addr.:

7ĆA, 7ĆB, 7ĆC

QDC module output to which you connect

your selected pressure control valve

FCC02ĆB06,B05,B04 = your selection

SCC02ĆB06,B05,B04 = your

selection

TCC02ĆB06,B05,B04 = your selection

B37/22, 21, 20

B37/86, 85, 84

B37/150,149,148

Your unselected setĆoutput values for outputs

1Ć4

FCC09Ć12 = your values

SCC09Ć12 = your values

TCC09Ć12 = your values

N43:5Ć8

N43:65Ć68

N43:125Ć128

All ramping is disabled with zero ramp rates

FCC17Ć20 = FCC25Ć28 = 0,

SCC17Ć20 = SCC25Ć28 = 0

TCC17Ć20 = TCC25Ć28 = 0

N43:13Ć16 N43:21Ć24

N43:73Ć76 N43:81Ć84

N43:133Ć136 N43:141Ć144

Pressure limits:

Minimum Control Limit

Maximum Control Limit

Selected Pressure Valve, Output for Min

Selected Pressure Valve, Output for Max

FCC41=SCC41=TCC41=0

FCC42=SCC42=TCC42=your value

FCC43=SCC43=TCC43=your value

FCC44=SCC44=TCC44=your value

N43:37, 97, 157

N43:38, 98, 158

N43:39, 99, 159

N43:40, 100, 160

8ĆA

Pressure vs. Position Control

CPC03ĆB04 = B02 = B00 = 1

B37/292, 290, 288

Logical bridge

CPC03ĆB10, B09, B08 = 0

B37/298, 297, 296

Mold Protection

CPC03ĆB11 = 0

B37/299

OpenĆloop control

CPC04ĆB07 = B05ĆB00 = 1

B37/311, 309Ć304

Expert Response Compensation (ERC) = Off CPC04ĆB15 = B13ĆB08 = 1

B37/319, 317Ć312

FCC pressure setpoints

CPC10, 13, 16 = your value

N43:246, 249, 252

FCC endĆofĆsegment position setpoints

CPC11, 14, 17 = your value

N43:247,250,253

Start LPC position

CPC61 = your value

N43:297

Mold Safe Position

CPC62 = your value

N43:298

If these are not your current values, we suggest that you correct them now
using the download procedure discussed in chapter 4.

FCC, SCC, TCC Profiles -

Pressure Valve(s)