Load Initial Profile Setpoints

Chapter 8

8-43

Continue Stroking or Stop and Notify

(EPC03)
Set this bit only if you your QDC module does NOT have control of all
valves required to change direction of ejector travel after each stroke.

- BIT 12 controls QDC module reaction when it completes any

advance or retract stroke during the ejector profile. The QDC
module:

0 = Runs the ejector profile without interruption
1 = At end of stroke:

* stops the ejector profile
* sets outputs
* notifies the PLC processor

Select this bit as follows, based on how you configured your ejector
hydraulic circuit.

Does the QDC module have control of all valves

required to change direction of ejector travel?

Then set

Bit 12 to

Then the QDC module;

And Your Ladder Logic Must:

Yes

0

Initiates each subsequent retract/advance stroke

upon completion of the preceding one.

Toggle DYC02ĆB14 (B35/414) to

command the QDC module to

execute the entire ejector profile.

For example: Direction of ejector travel is determined by a biĆdirectional flow valve connected to the QDC module.
No

1

* Stops the ejector profile

* Sets outputs to endĆofĆprofile setĆoutput values

* Notifies the PLC processor

Control directional valves NOT

connected to the QDC module to

assist executing the ejector profile.

For example: Direction of ejector travel is determined by uniĆdirectional flow valves connected to outputs controlled by the PLC processor.

We provide the following partial list of the interactive command and
status bits to help you program a stop-and-notify ejector profile in
your PLC ladder logic (for use when EPC03-B12 = 1).

Control Word: ProĆSet 600 address: Performs this action:

DYC02ĆB14

B35/414

Execute Ejector Profile

DYC03ĆB15

B35/431

Continue Ejector Profile

SYS03ĆB08

B35/40

Ejector Profile Stopped at EndĆof Stroke

SYS03ĆB10

B35/42

Ejector Forward Dwell Timer timing

SYS21ĆB14

B35/334

Ejector Profile in Progress

SYS22ĆB14

B35/350

Ejector EndĆof Advance setĆoutput in Progress

SYS22ĆB15

B35/351

Ejector EndĆof Retract setĆoutput in Progress

For additional ladder logic programming, refer to chapter 6.

Record a value for bit 12 accordingly on Worksheet 8-F.