Span Your Valves

Chapter 9

9-61

5.

Enable the ejector profile by setting DYC02-B14 (B34/414) to 1.
The ejector should move through its advance and retract stroke. If no
motion, verify that::

- none of your overtravel alarms are set. The QDC module inhibits

ejector profiles if SYS07-B00 through SYS07-B05 are set

- there are no programming error codes in SYS61 and SYS62

6.

Upon completion of the ejector profile, observe the velocities
reported for ejector advance and ejector retract segment 1 in EPS09
(N45:181) and EPS33 (N45:205). These velocities should be
relatively close to the setpoints you entered in EPC09 and EPC33
(N45:125, N45:149). If observed velocities are not within 25% of the
setpoints, verify that:

- you chose the correct values from your flow rate curves

- your calculations are correct

If the actual velocities are still not representative of your setpoints, your
flow valve is not linear over the range of your setpoints. Correct as
follows:

If:

And Your Selected

Valve is:

Then:

EPS09 was less than EPC09

Direct Acting

Increase EAC48 by 5%

Reverse Acting

Decrease EAC48 5%

EPS09 was more than EPC09 Direct Acting

Decrease EAC48 5%

Reverse Acting

Increase EAC48 by 5%

EPS33 was less than EPC33

Direct Acting

Increase ERC48 by 5%

Reverse Acting

Decrease ERC48 5%

EPS33 was more than EPC33 Direct Acting

Decrease ERC48 5%

Reverse Acting

Increase ERC48 by 5%

To do this: change EAC48 or ERC48, download the EAC or ERC block,
and repeat steps 4-6. Do this as necessary.

Important: If downloading from your programming terminal, download
EAC or ERC followed by EPC with download bits B21/21 or 22, and 23.