There are three ways of loading application files into PanelView terminals:

loading application files into user PROMs and installing the user

PROMs into the terminals

direct downloading of application files through the Upload/Download

cable. For installations where there are many PanelView terminals, this
requires going to each terminal, connecting the cable, and downloading
the application file

downloading application files over the Data Highway + network, using

the PLC-5 Pass-Through feature. Pass-Through Download Options lets
you do this in two different ways. You can use the parameters of a
resident application file configured for pass-through. Or you can
manually configure the parameters for the Address Source. The
advantage of using the PLC-5 Pass-Through feature is that the
development computer doesn’t have to be physically moved from
terminal to terminal, and the terminals don’t have to have their cabling
changed

To send a completed application file to a PanelView terminal, choose
Download to PanelView (RS-232) in the Transfer menu. To retrieve an
application from a PanelView terminal for modification, choose Upload
from PanelView (RS-232)
in the Transfer menu.

IMPORTANT: Before you can download or upload, you must be sure
that the communication settings on the PanelView terminal and in the
PanelBuilder software are exactly the same.

Setting Upload/Download Communications on the PanelView Terminal

To download or upload, communications must be established between the
PanelBuilder computer and the PanelView terminal. The default settings
(indicated in

Table 6.B

and

Table 6.C

) of the terminal and PanelBuilder are

matched. To change the communication settings for your PanelView
terminal, follow these steps:

1.

Set the PanelView terminal to Configuration mode.

2.

Choose Serial Port from the PanelView terminal Configuration
menu.

3.

Press Choose List to choose the “Upload/Download” list.

4.

Use the up and down cursor keys to move through the list, then use
the “Change Data” button to make your selection.

Methods of Loading

Application Files into

PanelView Terminals

Direct Downloading and

Uploading with the Upload

/Download Cable

Advertising