The Objects

Chapter 10

10-23

BCD: 4 bits

Bit: 9 bits; (all bits off = state 0) if more than one bit is on at a time, the

least significant bit’s state is displayed

The following table indicates the state number and the required bit pattern
for each data type:

Table 10.C

Bit Patterns for Each State: Binary, BCD and Bit Data Type

State

Binary

BCD

Bits

0

0000

0000

000000000

1

0001

0001

000000001

2

0010

0010

000000010

3

0011

0011

000000100

.

.

.

.

.

.

.

.

9

1001

1001

100000000

If the value indicated by the PLC controller is not within the indicator’s
range, the colors and attributes of the highest numbered state will be
displayed but the text inside the indicator will be blanked.

List Indicator

The List Indicator is used to display the current status or state of a
particular PLC operation. The list can have up to 24 items, one of which is
highlighted to indicate that it is currently in effect. The operator can see all
the possible states for a particular operation, and see which state is current.
The List Indicator is similar to the Control List Selector, except that the
PLC controller, rather than the operator, controls the display.

The value of the object’s PLC address, the state number, and the
configuration of Top Position Value determine which entry is highlighted.
This object supports three data types, binary, BCD, and bit. Like the
Control List Selector object and the Multi-State Indicator, the maximum
number of states is determined by the data type and the number of bits
assigned. See Table 10.B for a list of valid state values for states 0 to 9. If
more than one bit is on at a time, the least significant bit’s state is
displayed.