Troubleshooting

Appendix B

B-4

Table B.C lists the most common messages that can appear on a PanelView
terminal.

Table B.C

PanelView Major Fault Error Messages

Major Fault Message

Cause

What to do

Stuck Cell detected or Stuck Button

detected.

A touch cell or Keypad button has been

depressed for longer than the Stuck Button

Timeout setting allows.

Restart the terminal. If this problem occurs

repeatedly due to an operator holding the button

down for too long, increase the Stuck Button

Timeout setting in the Configuration menu.

If a button or cell is permanently stuck, call your

AĆB representative.

Watchdog Test Failed. Unit is disabled.

Watchdog circuit is unable to reset the machine. Servicing by AllenĆBradley is required.

System ROM corrupted. Unit is disabled.

The ROM containing the system firmware is

defective.

Servicing by AllenĆBradley is required.

RAM TEST failed. Unit is disabled.

The nonĆbackedĆup RAM used by the terminal

firmware is defective.

Servicing by AllenĆBradley is required.

Video hardware initialization failed. Unit is

disabled.

There is a video hardware problem.

Servicing by AllenĆBradley is required.

Mismatched application file. Unit is disabled. 1.) The application file is for the wrong type, i.e.,

a Keypad file on a Touch Screen terminal.

2.) The jumper settings are wrong

1.) Download an application file of the

appropriate type.

2.) Check the setting of JP5 (JP4 for Series C or

earlier terminals):

FB = Keypad

TS = Touch Screen

Failed to configure the Comm card. Unit is

disabled.

The Communication circuitry is faulty.

Servicing by AllenĆBradley is required.

Failed to stop PLC communication. Unit is

disabled.

The Communication circuitry is faulty.

Servicing by AllenĆBradley is required.

Application file corrupted.

The system has not stored the file correctly.

Download the file again or install new EEPROM.

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

Excessive external power cycles, noise or

voltage fluctuations.

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

Monitor power to terminal and take appropriate

power regulation and suppression actions.