Reducing plc addressing needs, Planning your application chapter 4, Examples of multiplexed objects – Rockwell Automation 2711 PANELBUILDER SOFTWARE USER MANUAL User Manual

Page 81

Advertising
background image

Planning Your Application

Chapter 4

4-6

Following is the maximum number of block transfers, data table words,
and bits available for PLC communication, when you assign from one to
five bi-directional block transfer files. This would be in addition to discrete
I/O words and bits.

Table 4.D

Block Transfer Data Table Words and Bits

No. of Block

Transfers

16 Bit Input

Words

16 Bit Output

Words

Total Input Bits

Total Output

Bits

БББББ

БББББ

1

БББББ

БББББ

32

БББББ

БББББ

32

БББББ

БББББ

512

БББББ

БББББ

512

БББББ

БББББ

2

БББББ

БББББ

64

БББББ

БББББ

64

БББББ

БББББ

1024

БББББ

БББББ

1024

БББББ

БББББ

3

БББББ

БББББ

96

БББББ

БББББ

96

БББББ

БББББ

1536

БББББ

БББББ

1536

БББББ

БББББ

4

БББББ

БББББ

128

БББББ

БББББ

128

БББББ

БББББ

2048

БББББ

БББББ

2048

БББББ

БББББ

5

БББББ

БББББ

160

БББББ

БББББ

160

БББББ

БББББ

2560

БББББ

БББББ

2560

You can reduce PLC address requirements by multiplexing—in other
words, using one screen object for more than one purpose, depending on
the state of a variable.

Normally you won’t need to multiplex objects—PanelView provides
plenty of separate I/O addresses as well as the capability for block transfers
and multiple racks. However, you can multiplex momentary push buttons,
numeric display data, and other objects.

Here are some examples:

Examples of Multiplexed Objects

Multiplexing a Momentary Push Button requires a second PLC address.
This is checked by the PLC program to determine how to interpret the push
button’s control bit. For example, you could have a List Selector’s input
address work as the multiplex address. The PLC program would then
check this address to decide how to respond when the button is pressed.

Multiplexing a Numeric Display and a List Selector—the List Selector’s
input address would work as the multiplex address. The PLC program
could check the value at the multiplex address before deciding which value
to put in the Numeric Display.

Reducing PLC Addressing

Needs