Using PanelBuilder

Chapter 3

3-38

Buttons and AutoĆRepeat

Three groups of buttons can have auto-repeat settings assigned. When
auto-repeat settings are changed from the default, the application will not
be compatible with version 1 firmware. For more information on version
control see Chapter 2, Installing Panel Builder.

Group 1 objects must be individually configured for auto-repeat when
each object is created. Group 1 objects include:

Increment and Decrement Buttons

Numeric Cursor Point Raise/Lower Function Keys

Set the Auto-Repeat Rate (per Sec.), Auto-Repeat Start Delay, and Amount
per Increment (for Increment buttons) or Amount per Decrement (for
Decrement buttons) under Address in the Object menu.

Group 2 objects are configured for auto-repeat as a group. Group 2 objects
include:

Screen List Selector Up/Down Cursor Buttons

Control List Selector Up/Down Cursor Buttons

Control List Selector with Enter Up/Down Cursor Buttons

Cursor Point Up/Down/Left/Right Function keys

Alarm Window Up/Down Cursor Buttons/Keys

Alarm History Screen Up/Down Cursor Buttons/Keys

Alarm Status Screen Line Up/Down Cursor Buttons/Keys

Cursor List Up/Down PgUp/PgDown Cursor Buttons

Set the Cursor Auto-Repeat Rate (per Sec.) and the Cursor Auto-Repeat
Start Delay under Options in the File menu. For group 2 objects, the
Amount per Increment is fixed at one.

Group 3 objects have a preset for auto-repeat which is not configurable.
Group 3 consist of the following objects in the Configuration Mode Menu
and the windows accessed from it:

Main Menu: Up/Down Cursor Buttons/Keys

Serial Port window: Change Data Button/Key

Serial Port window: Up/Down Cursor Buttons/Keys