Information and Alarm Windows

Chapter 7

7-36

Figure 7.30

Alarm Status Screen (in Display Active Alarms Mode)

22603

Change

Mode

Page

Down

Page

Up

Msg Accum Time Alarm

06/22/93

03:44:52 PM

#

Qty HH:MM:SS State

Message

Mode:

Display Active Alarms

1

5

00:02:18 ON

This is alarm message 1

Reset

Qty/Time

Print

Status

Line

Down

Additional alarms: Use PageĆUp or PageĆDown to view

Last QTY/TIME Reset occurred at: 06/21/93 14:07:35

Notes on the Alarm Quantity (Qty) and Accumulated Time (Accum

Time)

The Alarm Quantity (Qty) field shows the number of times the alarm has
gone into the alarm state. The field can display a maximum number of
9999. When the number of alarm transitions exceeds that, asterisks are
displayed: ****

The Accumulated Time (Accum Time) field keeps a record of how much
time each alarm has been on, i.e., in-alarm. The Accum Time field can
display an accumulated alarm time up to one second less than 100 hours
(99:59:59). When the accumulated time exceeds that maximum, asterisks
are displayed: **:**:**.

The Quantity and Accumulated Time fields for all alarm messages are reset
to zero when any one of the following occurs:

the PanelView terminal powers up (only when the Alarm Status

information is NOT battery-backed—see the section on the
Files/Options Menu in Chapter 3, Using PanelBuilder, for details on
User Memory Limits)

an application file is downloaded to the terminal

the

QTY/TIME Reset button on the Alarm Status Screen is enabled,

pressed, and confirmed