File Operations

Chapter 6

6-20

The other Location Data parameters can be configured through the
Communications menu before downloading, or in the Pass-Through
Download to PanelView window at the time of the transfer. Configurations
defined through the Communications menu are saved with the application
file and picked up automatically at the time of the download.
Configurations defined at the time of download override the configurations
in the application file, but they are temporary, and apply only to the current
PanelBuilder session.

PanelView/PLC DH+ Addresses

To configure the DH+ addresses defining the PanelView terminal location
and save them with the application file, choose Pass-Through
Configuration
in the Communications menu.

Figure 6.18

The PassĆThrough Configuration Window

22589

Pass-Through Configuration

PLC DH+ Address

Not Used

Local Bridge Address

Not Used

Remote Bridge Address

Not Used

Quit

Cursor to PLC DH+ Address and press Enter. The following window
opens:

Figure 6.19

PLC DH+ Address Window

22615

PLC DH+ Address

Not Used

PLC DH+ Address (0-77)

Quit

Cursor to PLC DH+ Address (0–77) and press Enter. Type the correct
address (in octal) in the small field that appears and press Enter.

Local Bridge Address/Remote Bridge Address

These fields are only required when you have two DH+ networks joined by
a connecting module or “bridge”. “Not Used” is the default entry in either
field; otherwise, enter the correct address in octal.