10ć26, The objects chapter 10, Set value button – Rockwell Automation 2711 PANELBUILDER SOFTWARE USER MANUAL User Manual

Page 291

Advertising
background image

The Objects

Chapter 10

10-26

Table 10.D

Input and Display Objects

Input Objects

Display Objects

Set Value Button

Numeric Data Display

Increment Value Button

Numeric Input Cursor Point

Decrement Value Button

Scrolling List

Keypad (Touch Screen Terminals)
KeypadĆEnable Button (Keypad Terminals)
Numeric Input Cursor Point

Table 10.E lists the capabilities of numeric objects, in terms of the decimal
points and negative sign—some objects can display the decimal point and
negative sign, and some cannot; some can accept the decimal point and/or
negative sign as part of the operator’s input, and some cannot.

Table 10.E

Decimal Point, Polarity Capabilities, and Data Ranges of Numeric Objects

Decimal Point

Polarity

Data Range

Set Value Button

N

N

0 - 99,999,999

Increment Value Button

N

N

0 - 99,999,999

Decrement Value Button

N

N

0 - 99,999,999

Keypad (Touch Screen

Terminals)

Y

Signed Integer

-32,768 - 99,999,999

KeypadĆEnable Button

(Keypad Terminals)

Y

Signed Integer

-32,768 - 99,999,999

Numeric Input Cursor

Point

Y

Signed Integer

-32,768 - 99,999,999

Numeric Data Display

Y

Y

-9,999,999 - 99,999,999

Scrolling List

Y

Y

-9,999,999 - 99,999,999

Set Value Button

The Set Value Button is used to set a PLC input address to a specific value
(a control value) with a single button press. Use this button if there is a
typical set point value that an operator might want to revert to frequently.
You can use a Set Value Button with Numeric Data Display and the
Increment and Decrement Buttons to change and monitor a value
associated with the Set Value Button.

Advertising