Information and Alarm Windows

Chapter 7

7-18

the message number must be between 1 and 496. The numbers do not

have to be created in ascending order, but they must be unique, i.e., no
two messages can have the same number

IMPORTANT: Importing an alarm message whose number is greater
than 256 will make the application compatible with Version 3 and later
terminals only.

the alarm text must begin and end with quotation marks

PanelBuilder will ignore any spaces found outside the quotation marks

PanelBuilder will ignore any character whose ASCII code is outside the

range 32–127. See Table 10.U for details of the ASCII character set

use the comment character (!) as the first character in the line of a

comment. PanelBuilder will ignore lines that begin with the !

make sure your message text is 50 characters or less.

IMPORTANT: Importing an alarm message whose length is greater than
36 characters will make the application compatible with Version 3 and later
terminals only.

when you name your file, use the extension .AMG

From the File menu, choose Windows. Then enable the Alarm Window
item. The Alarm Window menu opens. Choose Messages.

Figure 7.17

The Messages Window

23645

FILE MENU Screens Windows Options Communications Exit

Windows

Alarm Window

Enable

Information Window

Enable

Terminal Fault Window

Alarm History Screen

Alarm Status Screen

Numeric and Security Entry Window

Quit

Alarm Window

Messages

Window Type

Window Look

Window Control Address

Options

Quit

Messages

Select Message

1 [---] alarm number 1 is triggered

Create New Message

2

Delete Message

Copy Message to:

Import Message Text

Export Message Text

Quit