Troubleshooting

Appendix B

B-5

Table B.D

PanelView Minor Fault Messages

Minor Fault Message

Cause

What to do

Retentive data initialization failed.

There is no valid application file.

Go offĆline and download the file again.

Audio hardware initialization failed.

There is an audio hardware problem.

Servicing by AllenĆBradley is required.

Terminal can't keep up with activity.

Too much incoming data.

The operator should stop all input until the

PanelView Terminal can process data.

Invalid Powerup Screen.

Powerup screen does not exist or is faulty.

Reassign the Powerup Screen or check the

configuration data in the PanelBuilder

application file.

ББББББББББББ

Б

ББББББББББ

Б

Б

ББББББББББ

Б

Б

ББББББББББ

Б

ББББББББББББ

User EPROM/EEPROM is not installed or is

corrupted.

ББББББББББББ

Б

ББББББББББ

Б

Б

ББББББББББ

Б

Б

ББББББББББ

Б

ББББББББББББ

Optional EPROM or EEPROM was not found or

is faulty.

ББББББББББББ

Б

ББББББББББ

Б

Б

ББББББББББ

Б

Б

ББББББББББ

Б

ББББББББББББ

If no user EPROM or EEPROM is installed,

ignore this message. You can disable the test

and the message in the Configuration Mode

Menu.

If a user EPROM or EEPROM is installed,

replace it.

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

Battery test failed. User RAM will be lost on

power down.

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

The battery for application file memory is dead.

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

Upload the application file and save it on disk.

Servicing by AllenĆBradley is required.

ББББББББББББ

ББББББББББББ

Communication Self Test failed.

ББББББББББББ

ББББББББББББ

The communication card is defective or not

installed.

ББББББББББББ

ББББББББББББ

Servicing by AllenĆBradley is required.

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

Invalid Screen.

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

The PLC controller has selected a nonĆexistent

screen number.

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

Reprogram the PLC controller or the application

file.

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

Unable to write downloaded data to the

EEPROM.

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

The EEPROM or user memory configuration

jumpers are set incorrectly.

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

Check the EEPROM and user memory

configuration jumper settings.

ББББББББББББ

Б

ББББББББББ

Б

Б

ББББББББББ

Б

Б

ББББББББББ

Б

ББББББББББББ

Value Out Of Range.

ББББББББББББ

Б

ББББББББББ

Б

Б

ББББББББББ

Б

Б

ББББББББББ

Б

ББББББББББББ

Address not sufficient for data transfer.
Current screen number transfer to PLC

controller is not sufficient.
Numeric entry or display address length is

insufficient for data.

ББББББББББББ

Б

ББББББББББ

Б

Б

ББББББББББ

Б

Б

ББББББББББ

Б

ББББББББББББ

Increase bit length of address so it's large

enough for screen transfer, including Alarm

History and Alarm Status screens.
Increase address length for data.

PLC currently controls screen change.

PLC controller has control of screen change.

Disable PLC Controlled Screen Change.

Clear PLC Controlled Screen Change register.

Reset to 0.

No screen changeĊHold Time in effect or no

PLC Handshake.

Operator is trying to change screens while a

button's hold time is still in effect or before an

activated Latched Push Button has received a

handshake.

Wait until hold time is finished or Latched

handshake is received before trying to change

screens.