Installing the Decoder
Publication 2755-833
Use the Bulletin 1490-N1 conduit hub with the NEMA Type 4
decoder to maintain environmentally sealed connections at conduit
entrances. The NEMA Type 1 and Type 4 decoders accept Catalog
Number 1490-N1 conduit hubs (for a
7
/
8
inch hole size and
1
/
2
inch
conduit).
Conduit Holes
The conduit hubs install in the two output module field wiring holes
in the bottom of the enclosure. Each hole size is
7
/
8
inch and accepts
1
/
2
inch
conduit.
Conduit Connections
!
ATTENTION: To guard against enclosure damage,
align the conduit so as to prevent unnecessary stress on
the enclosure walls.
You can connect conduit to the conduit connector (hub) before or
after the conduit connector is secured into the prepared hole using
the connector locknut. Tighten connector locknut securely to provide
bonding to equipment enclosure.
!
ATTENTION: To complete the bonding between
grounding bushings and the enclosure, bonding must
be provided in accordance with all applicable codes.
Installing Conduit
Hubs/NEMA Type 4
Decoder
Conduit
”O” Ring
Outside
Enclosure
Enclosure
Locknut
Bulletin
1490
Conduit
Connector
(Hub)
Hole