Installing conduit hubs/nema type 4 decoder – Rockwell Automation 2755 Enhanced Decoder Series B User Manual

Page 61

Advertising
background image

4–22

Installing the Decoder

Publication 2755-833

Use the Bulletin 1490-N1 conduit hub with the NEMA Type 4
decoder to maintain environmentally sealed connections at conduit
entrances. The NEMA Type 1 and Type 4 decoders accept Catalog
Number 1490-N1 conduit hubs (for a

7

/

8

inch hole size and

1

/

2

inch

conduit).

Conduit Holes

The conduit hubs install in the two output module field wiring holes
in the bottom of the enclosure. Each hole size is

7

/

8

inch and accepts

1

/

2

inch

conduit.

Conduit Connections

!

ATTENTION: To guard against enclosure damage,
align the conduit so as to prevent unnecessary stress on
the enclosure walls.

You can connect conduit to the conduit connector (hub) before or
after the conduit connector is secured into the prepared hole using
the connector locknut. Tighten connector locknut securely to provide
bonding to equipment enclosure.

!

ATTENTION: To complete the bonding between
grounding bushings and the enclosure, bonding must
be provided in accordance with all applicable codes.

Installing Conduit
Hubs/NEMA Type 4
Decoder

Conduit

”O” Ring
Outside
Enclosure

Enclosure

Locknut

Bulletin
1490
Conduit
Connector
(Hub)

Hole