ANALOG TACH ZERO ADJ (P.202)

Used to remove any hardware-introduced offset from the analog tachometer feedback signal.
Typically, it will be 0.

Parameter Range:

-200 to + 200

Default Setting:

0

Parameter Type:

Tuneable

OIM Menu Path(s):

Speed/Voltage Loop (SPD)-Speed /Voltage Loop (SPD) Feedback

WARNING

The incorrect setting of this parameter can cause an overspeed condition. This parameter must be set

by a qualified person who understands the significance of setting it. Set the value of this parameter

accurately per your application requirements. Failure to observe this precaution could result in bodily

injury.

ANLG AUTO GAIN ADJ (P.101)

Used to scale the analog auto reference signal after it has been conditioned by the drive hardware.
Typically, it will be 1.000.

Parameter Range:

0.750 to 1.250

Default Setting:

1.000

Parameter Type:

Tuneable

OIM Menu Path(s):

Drive Reference - Drive Reference Scaling

ANLG AUTO SIGNAL TYPE (P.100)

Selects the analog auto reference signal type.

Parameter Range:

0 - 10V

+/-10V

4 - 20mA 10 - 50mA

Default Setting:

0 - 10V

Parameter Type:

Configurable

OIM Menu Path(s):

Drive Reference - Drive Reference Configure

Note: Jumpers J10 and J12 must be set for the type of auto reference selected.

ANLG AUTO ZERO ADJ (P.102)

Used to remove any hardware introduced offset from the analog auto reference signal.
Typically, it will be 0.
Parameter Range:

-200 to + 200

Default Setting:

0

Parameter Type:

Tuneable

OIM Menu Path(s):

Drive Reference - Drive Reference Scaling