APPENDIX B

FlexPak 3000

49’1340 e

B-26

MAXIMUM SPEED (P.004)

The maximum speed of the drive that can be supported by the application or process. MAXIMUM
SPEED can be less than or equal to TOP SPEED.
If raising this value causes MINIMUM SPEED to become less than 10% of MAXIMUM SPEED, an alarm
is generated.

Parameter Range:

1 to TOP SPEED (RPM or user-defined units)

Default Setting:

500 RPM

Parameter Type:

Tuneable

OIM Menu Path(s):

Drive Reference - Drive Reference Limits Quick Start

Refer also to Parameters:

TOP SPEED (P.011)

WARNING

The incorrect setting of this parameter can cause an overspeed condition. This parameter must be set

by a qualified person who understands the significance of setting it. Set the value of this parameter

accurately per your application requirements. Failure to observe this precaution could result in bodily

injury.

WARNING

When performing this adjustment, do not allow the motor to exceed the maximum safe speed of the

driven equipment as determined by the equipment manufacturer. Failure to observe this precaution

could result in bodily injury.

METER OUT 1 GAIN ADJ (P.400)

Scales the Meter 1 Output Signal at the regulator board terminal strip.

Parameter Range:

0.100 to 1.900

Default Setting:

1.000

Parameter Type:

Tuneable

OIM Menu Path(s):

Input/Output - Meter Outputs

NOTE: Testpoint METER OUT FULL SCALE must source METER OUT 1 SELECT for an accurate
adjustment. See Appendix D, figure D.8, for further details.