APPENDIX B

FlexPak 3000

49’1340 e

B-14

DIG OUT 2 SELECT (P.411)

Only available if the I/O Expansion Kit is installed. Selects the signal used to drive digital output 2
(terminals 68 and 69 on the I/O Expansion board).

DANGER

This output is intended for use as an indication. If it is used as a control source, a dangerous condition

can result. Failure to observe this precaution can result in severe bodily injury or loss of life.

Parameter Range:

LEVEL DETECT 1 OUTPUT,

LEVEL DETECT 2 OUTPUT,

IN CURRENT LIMIT,

DRIVE READY,

NETW COMM STATUS,

NETW IN REG 1 (bit 1),

NETW IN REG 2 (bit 1),

NETW IN REG 3 (bit 1),

Default Setting:

LEVEL DETECT 2 OUTPUT

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Digital I/O

Refer also to Parameters:

LEVEL DETECT 1 OUTPUT (P.648), LEVEL DETECT 2 OUTPUT (P.649)
NETW COMM STATUS (P.908),

NETW IN REG 2 (P.906),

NETW IN REG 3 (P.907)

ENHANCED FLD VOLT ADJ (P.500)

Adjusts the field output voltage if the Enhanced Field Supply is used. (This parameter does not effect
the operation of the standard or current regulated field supplies).

Parameter Range:

0 to 180 (J21 set to B-C)

Default Setting:

84 V

Parameter Type:

Tuneable

OIM Menu Path(s):

Field - Standard/enhanced Field Supply

Refer also to Parameters:

FLD CURRENT REGULATOR (P.586).

Increasing ENHANCED FLD VOLT ADJ causes the voltage at the 3C and 3D terminals to increase;
decreasing decreases the output voltage. This parameter has no effect when the output parameter
FIELD ECONOMY ACTIVE = ON (i.e., when the drive is in field economy). This parameter is not
available if the Field Current Regulator is installed.

FEEDBACK SELECT (P.200)

Selects the type of feedback signal that is used for the speed/voltage loop. PULSE TACH can be
selected only if a pulse tachometer kit is installed.
NEGATIVE CURRENT LIM is set to 0 and REVERSE DISABLE is set ON if:

AC TACH is selected.

PULSE TACH is selected and PULSE TACH QUAD is set OFF.

Parameter Range:

ARMATURE VOLT,

DC TACH,

PULSE TACH,

AC TACH

Default Setting:

ARMATURE VOLT

Parameter Type:

Configurable

OIM Menu Path(s):

Speed/Voltage Loop (SPD) - Speed Voltage Loop (SPD) Feedback
Quick Start

Refer also to Parameters:

NEGATIVE CURRENT LIM (P.006),

REVERSE DISABLE (P.015)

WARNING

The incorrect setting of this parameter can cause an overspeed condition. This parameter must be set

by a qualified person who understands the significance of setting it. Set the value of this parameter

accurately per your application requirements. Failure to observe this precaution could result in bodily

injury.