TROUBLESHOOTING/DIAGNOSTICS

49’1340 e

FlexPak 3000

7-3

Pressing ENTER will display details and possible causes of the specific fault log entry.

F00009: CONTROLLER THERMOSTAT TRIP
028 days 14 hours 30 mins 00 secs

Controller thermostat indicates high temperat.
Possible causes:

#

Inadequate heat sink ventilation

!!
!!

Fault
Alarm
Interlock OK
Drive Ready
Running
Current Limit
Torque Limit

FAULT

KEYPAD MANUAL FORWARD

#

Indicates that more information is available. To view this information, press the down arrow

key. The remaining text for this specific fault will be displayed when scrolling takes place:

Inadequate cabinet ventilation.
Heat sink failure.
Damaged or disconnected controller thermostat wiring.

7.7.1.2

Reset Faults

Pressing ENTER with the cursor at Reset Faults extinguishes the Fault indicator and displays
the following message on the OIM display:

ATTENTION!
DRIVE FAULTS HAVE BEEN RESET.
Press CANCEL to continue.

Resetting faults allows the user to try restarting the drive. NOTE: If proper steps were not taken
to correct the fault before reset, another Fault will occur. Press CANCEL to continue.

Faults can also be reset by pressing the STOP/RESET key when the drive is stopped and CSS
= KEYPAD.

7.7.1.3

Clear Fault Log and Reset Faults

Pressing ENTER with the cursor at Clear Fault and Reset Faults extinguishes the Fault
indicator, resets drive faults and displays the following message on the OIM display:

ATTENTION!
DRIVE FAULTS HAVE BEEN RESET.
FAULT LOG HAS BEEN CLEARED.
Press CANCEL to continue.

7.7.2

About The Alarm Menu

Access the Alarm Menu by pressing the FAULT key until ALARM appears on the OIM directly
above the FAULT key. The following will be displayed.

Alarm Menu

Review Log

Reset Alarms
Clear Alarm Log and Reset Alarms

!!
!!

Fault
Alarm
Interlock OK
Drive Ready
Running
Current Limit
Torque Limit

ALARM

KEYPAD MANUAL FORWARD