APPENDIX B

49’1340 e

FlexPak 3000

B-25

LEVEL DETECT 2 SELECT (P.605)

Selects the signal that drives level detector 2. See LEVEL DETECT 1 SELECT for discussion and block
diagram.

Parameter Range:

SPD SOURCE SELECT OUT

SPEED RAMP INPUT TP

SPEED RAMP OUTPUT

SPD LOOP FEEDBACK

CML FEEDBACK

Default Setting:

SPEED RAMP INPUT TP

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Level Detectors

Refer also to Parameters:

LEVEL DETECT 1 SELECT (P.602), LEVEL DETECT 2 DELAY (P.607),
LEVEL DETECT 2 OUTPUT (P.649), LEVEL DETECT 2 THRESH (P.606)

LEVEL DETECT 2 THRESH (P.606)

The threshold for level detector 2. See LEVEL DETECT 1 SELECT for discussion and block diagram.

Parameter Range:

0.1 to 100.0% or MAXIMUM CURRENT %*

Default Setting:

10.0%

Parameter Type:

Tuneable

OIM Menu Path(s):

Input/Output - Level Detectors

Refer also to Parameters:

LEVEL DETECT 1 SELECT (P.602), LEVEL DETECT 2 DELAY (P.607),
LEVEL DETECT 2 OUTPUT (P.649), LEVEL DETECT 2 SELECT (P.605),
MAXIMUM CURRENT (P.007)

*The parameter range for the level detector is automatically rescaled for speed or current based on the
input selected by LEVEL DETECT 2 SELECT. If CML FEEDBACK is selected for LEVEL DETECT 2
SELECT, the parameter range is 0.1 to MAXIMUM CURRENT. For any other LEVEL DETECT 2
SELECT settings, the parameter range is 0.1 to 100.0%.

MANUAL REF SELECT (P.106)

Sets the reference for the speed/voltage loop when the drive is in manual mode and CONTROL
SOURCE SELECT is set to TERMBLK. If the I/O Expansion kit is not installed, this parameter is fixed to
ANALOG. This parameter is not accessible over the network.
When set to ANALOG, the analog MANUAL reference input (terminals 16, 17 and 18 on the regulator
board) is the reference.
When set to MOP, MOP OUTPUT parameter is the reference.

Parameter Range:

ANALOG
MOP

Default Setting:

ANALOG

Parameter Type:

Configurable

OIM Menu Path(s):

Drive Reference - Drive Reference Configure

Refer also to Parameters:

CONTROL SOURCE SELECT (P.000)

MOP OUTPUT (P.191)

MAXIMUM CURRENT (P.007)

The highest amount of current (positive or negative) for a given application.
This input is used as the basis of armature current scaling.
MAXIMUM CURRENT is limited to 200% of MOTOR RATED ARM AMPS (P.008).

Parameter Range:

25 to 200% of P.008

Default Setting:

150%

Parameter Type:

Configurable

OIM Menu Path(s):

Current Minor Loop (CML) - CML Feedback Scaling

Refer also to Parameters:

MOTOR RATED ARM AMPS (P.008)